Missing Smoke Seals: Why Detection Cannot Replace Containment

Some Kingsway FD30S and FD60S doorsets shipped without smoke seals. A 30-minute fire rating does not guarantee 30 minutes of breathable escape route.

Products and Services

Review relevant products, system options, application guidance, project support, and pre-sales or after-sales services.

Information for Selection

Compare the application scenario, functional requirements, installation environment, interfaces, communication method, quantity, and project schedule.

How Information Is Verified

Confirm model numbers, technical parameters, certifications, delivery terms, and compatibility against current product documents and agreed project requirements.

Key Takeaway

Some Kingsway FD30S and FD60S doorsets shipped without smoke seals. A 30-minute fire rating does not guarantee 30 minutes of breathable escape route.

Why it mattersUse the article to identify the technical, market or project decision affected.
Check the evidenceFollow named standards, tests, product documents and dated primary sources.
Before actingVerify the current rule, jurisdiction, certificate scope and project conditions.

Evidence and decision context

This report should help readers identify what changed, who may be affected and which primary documents or current product records must be checked before a decision.

Direct answer: On 18 November 2026 the UK notified a safety report on Kingsway SOLO FD30S and FD60S single-action doorsets because some units were shipped without the smoke seals that the S suffix promises. The doors still resist fire, but smoke can pass around them in the first minutes of an incident, which is precisely when an escape route is in use.

Key points

  • The affected models are the smoke-control versions only, identified by the S suffix in FD30S and FD60S; the standard fire-only doorsets are outside the notice.
  • Without seals, cold smoke migrates through the perimeter gaps of a closed door before the leaf heats up, so a 30-minute fire rating does not deliver 30 minutes of tenability.
  • The manufacturer has begun a modification programme to fit the missing seals at no cost to affected sites, and advises that doors be kept closed with self-closers verified in the meantime.

Why this matters

Detection and compartmentation are usually specified by different people and inspected by different contractors, which is how a building ends up with excellent alarm coverage and doors that leak smoke. A closed door with a missing seal is not a small defect: in a stair or protected lobby it lets smoke into the escape route while occupants are still descending.

For alarm manufacturers the lesson is one of scope. A detector is specified to warn, not to contain, and no sensitivity setting compensates for a door that will not hold smoke. The same logic applies to the products around the door: a magnetic hold-open device released by the fire alarm is only useful if the leaf closes onto a sealed frame,.

Technical details: fire rating and smoke rating are different tests

A doorset rated FD30 or FD60 is tested to BS 476-22 or BS EN 1634-1 for integrity and, where claimed, insulation. The S suffix adds a smoke-control claim, which is assessed against the leakage criteria of BS EN 1634-3 for ambient and medium temperature smoke. The test measures leakage through the assembly at a defined pressure differential, and the seal is the component that does the work. Remove it and the leaf can still pass an integrity test while failing the smoke criterion outright.

In North American practice the equivalent documents are NFPA 105 for smoke door assemblies and NFPA 80 for fire doors, with leakage classified under UL 1784. NFPA 80 requires an annual inspection of fire door assemblies, including confirmation that labels are present, that clearances are within tolerance, and that self-closing hardware functions. NFPA 72 then assumes the door will do its job when it coordinates alarm notification with door release.

How US and UK duty holders should read the notice

In the United States the obligation sits with the building owner under NFPA 101, with the annual NFPA 80 inspection as the evidence trail. In Great Britain the Responsible Person must act on the notice under the Regulatory Reform (Fire Safety) Order 2005, and the product itself may fall short of the General Product Safety Regulations 2005.

First, identify affected doors by label and model rather than by memory, because the S suffix is easy to overlook on a schedule. Second, verify that each leaf closes fully into its rebate and that the self-closer latches from a partially open position. Third, keep a written record of the interim measure, since a risk assessment that notes an open defect and a compensating control is defensible, while an undocumented defect is not.

Specification advice

When specifying doorsets, require the smoke leakage classification to be stated on the label, not only in the datasheet, and ask for the test report that covers the exact leaf, frame and seal combination being supplied. Seals are the component most often substituted during value engineering, and a substitute invalidates the tested configuration. Our certification library and detection product range are structured around the same principle: the claim on the label should be traceable to a test report that covers what was actually installed.

Frequently asked questions

How can I tell whether a door has smoke seals?

Look at the frame rebate and the leaf edge with the door closed. An intumescent strip is usually a thin, dark, graphite-filled line, often combined with a flexible blade or brush seal. If the only line present is intumescent and there is no flexible gasket, the assembly has fire sealing but not smoke sealing, and the S suffix claim is not being delivered.

Does a door closer remove the need for seals?

No. A closer ensures the leaf returns to the frame; it does not close the gap between leaf and frame. Typical perimeter clearances of two to three millimetres are enough to pass measurable smoke at the pressure differences found in a stairwell during a fire, which is why the seal, not the closer, carries the smoke performance.

Can more detectors compensate for a leaking door?

Only in the sense that earlier warning gives occupants more time. Detection cannot restore a contaminated escape route once smoke has entered it. If a protected corridor is leaking, the correct remedy is the door assembly, and detector spacing should be reviewed afterwards rather than used as the substitute.

Reviewed by the Wanlin Fire technical team. Sources: OPSS report 2611-0072.